3M™ Cold Shrink QT-III Silicone Rubber IndoorTubular Termination KitWith High-K Stress ReliefFor Tape Shield, Wire Shield and UniShield® Cable7622-T-110, 7623-T-110, 7624-T-110, 7625-T-110,7626-T-110InstructionsIEEE Std. No. 48Class 1 Termination15 kV Class110 kV BILF CAUTION Working around energized systems may cause serious injury or death. Installation shouldbe performed by personnel familiar with good safety practice in handling electricalequipment. De-energize and ground all electrical

No Özeti sayfasında içerik 2

1.0 Kit Contents3 High–K, Tracking Resistant, Silicone Rubber Terminations3 Pre-formed Ground Braids3 Constant Force Springs3 3M™ EMI Copper Foil Shielding Tape 1181 Strips, 1/2" x 10"6 Strips Scotch® Mastic Strip 2230 (black with white release liners, bagged)1 3M™ Cable Cleaning Preparation Kit CC-21 Instruction SheetNote: Do not use knives to open plastic bags.Kit Selection TableNOTE: Final Determination Factor is cable insulation diameter.Conductor Size Range (AWG & kcmil)Primary Insul

No Özeti sayfasında içerik 3

2.0 Instructions for Tape Shielded CablePrepare Cable2.1 Check to be sure cable size fits within kit range as shown in Table 1.2.2 Prepare cable using dimensions shown in Figure 1. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG.If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M™ EMI Copper FoilShielding Tape 1181.NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs orconnectors as follows:Aluminum Lugand

No Özeti sayfasında içerik 4

3.2 Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASENOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid,extending over cable jacket with solder block over mastic strip (Figure 3). Secure ground braid to cable jacket 4-1/2"(114 mm) from cable semi-con edge using vinyl tape (Figure 3).NOTE: Position vinyl tape with care, it also serves as a marker for positioning the

No Özeti sayfasında içerik 5

3.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around Scotch® Mastic Strip 2230,constant force spring and exposed tape shield (Figure 5).NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELDIn cables with cloth or paper semi-conductive shields, it is recommended the ®shield be over wrapped with one halflapped layer of highly stretched semi-conductive ru

No Özeti sayfasında içerik 6

6.0 Install Termination6.1 Slide the termination body onto the cable and remove core. Make sure the termination body (not the core) is buttedup to the edge of the vinyl tape marker previously applied (Figure 7). Pull the core while unwinding, counterclockwise, starting with the loose end (Figure 7). Be sure to alternate the pulling and unwinding actions (pullunwind-pull-unwind-etc.) to help prevent the core material from binding up as the core is being removed.NOTE: Once the termination body mak

No Özeti sayfasında içerik 7

Instructions for Wire Shielded Cable7.0 Prepare Cable7.1 Check to be sure cable size fits within kit range as shown in Table 1.7.2 Prepare cable using dimensions shown in Figure 8 and Figure 9. BE SURE TO ALLOW FOR DEPTH OFTERMINAL LUG.NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs orconnectors as follows:Aluminum Lugand ConnectorGrowth Allowance2 - 3501/4” (6 mm)400 - 6501/2” (13 mm)750–10003/4” (19 mm)1250 - 2000Field determin

No Özeti sayfasında içerik 8

8.0 Install Ground Braid8.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLEWRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess.1/4" (6 mm)Semi-Con1st Scotch Mastic Strip 2230®Cable JacketFigure 108.2 Position pre-formed ground braid with short tail over wire shield directly adjacent to cable jacket cut edge. Positionlong tail of ground braid, extending over cable jacket with solder block ov

No Özeti sayfasında içerik 9

8.3 Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in placewith constant force spring. Wrap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring afterwrapping the final winding.8.4 Select second Scotch® Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAPof mastic over solder block on ground braid and previously applied mastic (Figure 12). Cut off excess.Constant Force SpringT

No Özeti sayfasında içerik 10

9.0 Install Lug or Connector Important Packaging NoticeIn order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packedwith a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install thetermination. This shipping core can be recycled with other polypropylene waste9.1 Check to insure 3M™ Cold Shrink QT-III Silicone Rubber Termination fits over the selected lug or connector. Iflug or connector (Figure 1

No Özeti sayfasında içerik 11

11.2 Connect ground braid to system ground according to standard practice.Correct Installation of Termination on Wire Shielded CableVinyl TapeMarkerRidge at End of CableInsulation Shield (Semi-Con)Ridge at Endof High-K TubeCable InsulationSemi-Con Insulation ShieldEnvironmental TopSealConductorStress Controlling CompoundHigh-K StressRelief TubeInstructions for UniShield® Shielded Cable12.0 Prepare Cable12.1 Check to be sure cable size fits within kit range as shown in Table 1.12.2 Prepare cable

No Özeti sayfasında içerik 12

12.4 Remove constant force spring. Bend shield wires back upon cable jacket 1-1/2" (38 mm). Cut excess shield wire anddiscard (Figure 17).Depth Of Terminal Lug + Growth Allowance9" (229 mm)1-1/2" (38 mm)Semi-Conductive JacketFold Back Shield WiresFigure 1712.5 Remove semi-conductive jacket to dimension shown in Figure 18.NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring-cut 80% through jacket.Remove jacket sections by pulling against constant force spring

No Özeti sayfasında içerik 13

13.0 Install Ground Braid13.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLEWRAP of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires (Figure 19). Cutoff excess.1/4" (6 mm)Semi-ConShield Wires1st Scotch® Mastic Strip 2230Figure 1913.2 Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. Position long tailof ground braid, extending over cable semi-conductiv

No Özeti sayfasında içerik 14

Constant Force SpringShield WiresGround BraidTrim1st Scotch Mastic Strip 2230®Solder BlockCableWireShield2nd Scotch® Mastic Strip 2230Ground Braid LegFigure 2113.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force springand exposed shield wires (Figure 22).NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.1-1/2" (38 mm)Semi-ConShield WiresConstant Force SpringTwo Half-Lapped Laye

No Özeti sayfasında içerik 15

NOTE: Refer to pages 17-19 for 3M ™ connector and lug crimping information.NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Insertconductor into lug or connector and then remove conductor. This will transfer some of the antioxidant compound ontothe conductor. Wire brush the anti-oxidant paste into the strands. Immediately insert conductor into lug or connectorbarrel as far as it will go.NOTE: Die/crimper head rotation between consecutive c

No Özeti sayfasında içerik 16

Correct Installation of Termination on UniShield® Shielded CableVinyl TapeMarkerRidge at End of CableInsulation Shield (Semi-Con)Ridge at Endof High-K TubeSemi-ConCable InsulationStress Controlling CompoundConductorEnvironmental TopSealHigh-K StressRelief Tube 16 78-8113-5099-6 Rev E

No Özeti sayfasında içerik 17

Tooling IndexLug and Crimping Information for 3M™ Scotchlok™ Copper Lugs30014 thru 30045One hole31145 thru 31178Two hole-long barrel31036 thru 31068One hole-long barrelCableSize AWG/kcmilStudSize(in.)3M™Scotchlok™Copper LugNumber6101/45/164Crimping Tool-Die Sets (Minimum Number Of Crimps)Burndy CorporationThomas & Betts CorporationSquare D Co.Anderson Div.MD6MY29Y34AY35, Y39,Y45*, Y46*TBM 5TBM 8TBM 15VC6–3,VC6–FT**300143001530016–6AWG(1)–U5CRT(1)Blue(1)Blue(1)–(1)101/43/8300183

No Özeti sayfasında içerik 18

Tooling IndexLug and Crimping Information for 3M™ Scotchlok™ Copper/Aluminum Lugs40016 thru 40079One hole40132 thru 40178Two holeCable Size AWG/kcmilStud Size (in.)3M™ Scotchlok™Lug NumberCrimping Tool-Die Sets (Minimum Number Of Crimps)MD665/1640016W161(1)6AWG(1)A6CAB(1)U6CABT(1)(1)Grey(1)Grey(1)–29(1)(1)–BY19(3)J(3)45/1640020W162(3)4AWG(1)A4CAB(1)U4CABT(1)(1)Green(2)Green(2)–37(1)(1)–BY53(3)P(3)3/840024W163(3)2AWG(1)A2CAB(1)U2CABT(1)(1)Pink(2)Pink(2)42H(2)(1)BY23(3)1/2(3)1/2400

No Özeti sayfasında içerik 19

Tooling IndexCrimping Information for3M™ Stem ConnectorsCopper/AluminumConductor SizeAWG & kcmilStranded2, 141/02/03/04/0Solid1, 1/022/03/04/0–Crimping Table For 3M™ Stem Type Connector3M ConnectorNumberRecommended Crimping Tools™SC0001SC0002SC0010SC0020SC0030SC0040ManufacturerMech. ToolDie (Minimum No.Crimps)HydraulicDie (Minimum No.Crimps)BurndyMD6BG(4), W241(3)Y35, Y39, Y45*, Y46*U25ART(2), U243(2)Kearny0–51, 0–525/8–1 (4)WH–1, WH–25/8–1(4)T&BTBM 5Tan(2)––T&BTBM 8Olive

No Özeti sayfasında içerik 20

3M, Scotch and Scotchlok are trademarks of 3M Company.UniShield is a trademark of General Cable Technologies Corporation.Important NoticeAll statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable,but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable foryour intended application. You assume all risks and liability associated with such use. Any sta